Low suction pressure high head pressure - I was working on a water source heat pump Trane serial number# W04C11546 MN# GEVB02411J0110TL. The unit is an upflow with the compressor compartment being on the bottom and the fan and coil on top. The problem is that the unit will run for about one minute in cooling mode then goes off on high head (400 psi r-22). …

 
Pressure gauges provide readings of the condensing and suction pressures, allowing technicians to monitor and adjust the head pressure as needed. B. Measuring Head Pressure in Refrigeration Systems To measure head pressure in refrigeration systems, technicians connect pressure gauges to the service ports on the high and low sides of the system.. Kroger lake jackson texas

After the system runs for a while, raise the RPMs up to about 1,500. The system should be about 25 to 30 psi on the low side and 200 to 250 psi on the high side. If the ambient temperature is higher or lower than normal (70 to 80°F) the pressures will go …Low suction/High head. I have a carrier 38QRF024300 with a 40QNQ024 unit I be been having issues with. Originally my readings were 157# suction (410A) and 275# head reading 7,5.2, and 4.1 amps when RLA is 12.8; with 5 degrees of subcooling. Ambient is 80 in parking garage.Study with Quizlet and memorize flashcards containing terms like The technician finds a high split across an evaporator coil this is an indicator of what?, The technician observes low gauge pressures on an AC unit this is an indicator of?, You find superheat by subtracting suction temperature from suction pressure T/F? and more.In addition to a malfunctioning TXV, other factors that can cause high subcooling include a dirty condenser coil or restricted airflow over the condenser. Low Suction pressure/ low head pressure. A bad TXV can also cause low suction pressure and low head pressure in an HVAC system by restricting the flow of refrigerant into the evaporator coil.May 8, 2017 · Table 1: R134a Saturation Properties pressure table (Reference: www.chemours.com) Back to the problem at hand. For any refrigeration cycle/AC unit there are two operating pressures: suction pressure and discharging pressure, high and low settings for each pressure line determined by the manufacturer will stop the unit. R410a suction pressure may be around 120psi, and R410a head pressure may be anywhere from 225psi to 350psi. Many conditions could apply here, there’s absolutely ‘no’ set point pressure for 410a, r22, or anything else. Educate yourself on whats going on in the heat transfer process.Study with Quizlet and memorize flashcards containing terms like The technician finds a high split across an evaporator coil this is an indicator of what?, The technician observes low gauge pressures on an AC unit this is an indicator of?, You find superheat by subtracting suction temperature from suction pressure T/F? and more.And, just as common, is suction pressure and/or head pressure being involved in the cause. Often, the refrigeration system will still run, but it’ll run inefficiently because the suction pressure is too high while the head pressure is simultaneously too low. ... Compressor amperes: low. Low side pressure: 11.6 psig/10° High side …Mar 24, 2023 · In addition to a malfunctioning TXV, other factors that can cause high subcooling include a dirty condenser coil or restricted airflow over the condenser. Low Suction pressure/ low head pressure. A bad TXV can also cause low suction pressure and low head pressure in an HVAC system by restricting the flow of refrigerant into the evaporator coil. R22 boiling point: -40.8 degree Celsius at atmospheric pressure (sea level or 1 ATM) R22 density: 3.66 g/cm 3, in gas form - this is a colorless gas. R22 molar mass: 86.47 g/mol. R22 gas cylinder identification: light green. R2 status: no longer in active use, replaced with R458A.lower suction pressure and high discharge pressure. Study with Quizlet and memorize flashcards containing terms like which of the following is NOT a symptom of a hermetic system that is low on refrigerant?, frost on the suction line indicates;, an increase in head pressure causes _____ refrigerant to flow through a capillary tube. and more.If a high head pressure is detected, you will need to call your local professionally licensed air conditioning service team. What Determines High Head Pressure. A 410A system who have 400-418 PSIG on the high side, while the lower side is 120-130 PSI. If it is more than this, it is considered high.Our diagnostic sheet shows that liquid line restrictions cause low suction pressure and normal to low head pressure, not high head pressure.When the emit gasses facing leakage due to the piston ring of the compressor the pressure is developed than the normal pressure and the high suction …How to Check Subcooling. Attach the thermometer to the liquid line. This time, near the condenser. Then take the head pressure in Psi and convert it to the temperature on the pressure/temperature chart. Assuming you are dealing with a R22 system, let’s say the head pressure is 260Psi. This will convert to 120F.Wakra is a beautiful coastal city in Qatar that is known for its stunning beaches and crystal-clear waters. For beach enthusiasts, one important factor to consider before heading o...High Suction Pressure R-410a. i went to check an 3.5 ton a/c brand is a ICP (international comfort products) Model WAPL424A1, not cooling my pressures were low side 185 to 190 and high side was around 350 on a 107F hot day. It has a piston as a metering device and compressor was running at 11.50 amps and RLA is 17.25 amps.So we replace the compressor (same model #), replace the liquid line filter dryer, and evacuate to 500 microns. I weigh the charge in per the manual = unit's orignal charge + addl ounces per foot of lineset - total of 5# 6 oz. Start unit up, damn it, looks wrong immediatelY: Suction: 149.5 psi. Suction Temp: 55.4*F.404a pressures in low. I have a r-404a roof-top condensing serving a walk in freezer. pressures are 235 psi head pressure and a 28psi suction pressure. Outdoor ambient is 30degress and indoor box temperature is about 20degrees. System has a head pressure control on roof for hot gas. Wondering if pressures sound right.33 posts · Joined 2011. #7 · Jul 4, 2011. " high head, low suction". 310 isn't high, unless the outdoor temp is 70F which probably isn't the case. Typical condensing temps for 13 SEER cooling equipment is 15-20 degrees above outdoor temp. The saturated temp for 310psi is right at 99F.Watch on. Compression ratio is the ratio of head pressure to suction pressure in an HVAC/R unit. Generally, compression ratios approach 2.5:1 on high-efficiency, 16+ SEER A/C systems. The highest compression ratio in A/C compressors is typically 11:1. Refrigeration compression ratios tend to be quite a bit higher (up to 26:1).Mar 13, 2017 · NPSH Required (NPSHR): The minimum pressure required at the suction port of the pump to keep the pump from cavitating. NPSH or Net Positive Suction Head is a very important part of a pumping system. The systems NPSH A must be higher than the pump’s NPSH R in order for proper pump performance and to eliminate the risk of cavitation, which can ... And, just as common, is suction pressure and/or head pressure being involved in the cause. Often, the refrigeration system will still run, but it’ll run inefficiently because the suction pressure is too high while the head pressure is simultaneously too low. ... Compressor amperes: low. Low side pressure: 11.6 psig/10° High side …Pressure gauges provide readings of the condensing and suction pressures, allowing technicians to monitor and adjust the head pressure as needed. B. Measuring Head Pressure in Refrigeration Systems To measure head pressure in refrigeration systems, technicians connect pressure gauges to the service ports on the high and low sides of the system.Are you confused about all the different blood pressure readings? You aren’t alone. Read this quick guide to learn more about the difference between systolic and diastolic, what no...Comparing head pressure with suction pressure reveals much about an HVAC unit. High or low readings indicate potential issues. Regular checks help catch problems early. For example, if head pressure is too high but suction remains normal, there might be a blockage. Conversely, low head pressure could suggest a leak somewhere in the system.When measuring evaporator superheat on a commercial system that has a long suction line, the pressure reading should be taken at the A. Compressor inlet B. Evaporator outlet C. Condenser ... A TXV with an external equalizer is used on A. Evaporators with a high pressure drop B. Evaporators with a low pressure drop C. High temperature ...Dec 20, 2023 · A blockage causes high head pressure while suction pressure remains low. This imbalance puts strain on the compressor and reduces cooling efficiency. To troubleshoot, technicians will check for dirty filters, malfunctioning expansion valves, and debris in condenser coils. Clearing these blockages restores proper function to the refrigeration cycle. Low suction/High head. I have a carrier 38QRF024300 with a 40QNQ024 unit I be been having issues with. Originally my readings were 157# suction (410A) and 275# head reading 7,5.2, and 4.1 amps when RLA is 12.8; with 5 degrees of subcooling. Ambient is 80 in parking garage.Very high suctuion and head pressure on heating mode. Hello, I have a Rheem (2015) heat pump 2ton 410A, on cooling mode the system runs great; suction and liquid pressure are ok 185/360, super heat 10 F, with 90F outdoor temperature, now the winter is coming and the system on heating mode the gages read high pressure on both sides, begin from ...Low suction pressure and high head pressure occur when there’s a drop in refrigerant pressure in the AC system, coupled with elevated output pressure in the …Jun 14, 2012 · 410A System with high head. I went to do a maintenance on a 410A Trane system today, when I came up on the trane I noticed it was running like a 450 pound head pressure, the first thing i thought was why in the world would it be so high, so I cleaned the cool, checked filters, checked txv bulb position, everything checked out although there ... I just wanted to pick every ones brain i could. I am working on trane condensor and have high head pressure and low suction pressure. It was 90+ out today and I dumped r-22 into the system and no matter what I did I could not get the suction line to sweat and the superheat never dropped below about 20 degrees. my head pressure …Are you confused about all the different blood pressure readings? You aren’t alone. Read this quick guide to learn more about the difference between systolic and diastolic, what no...Your blood pressure readings are useful indicators of your cardiovascular system’s overall health. Low, high and normal blood pressure readings help your doctor make the right deci...A cold suction line (low superheat) with low suction pressure is a symptom of low evaporator air. A liquid restriction would result high superheat (warm suction line). The high head probably due to the other guys overcharging, trying to get the suction pressure up.Low suction pressure causes. low suction pressure is developed in the refrigeration system. Some of the most probable causes are as below, The coil is covered with dust or frost. Restriction in the refrigerant line. Filters and strainers are dirty. Faulty fan motor. Low room temperature. Faulty compressor.Low suction/High head. I have a carrier 38QRF024300 with a 40QNQ024 unit I be been having issues with. Originally my readings were 157# suction (410A) and 275# head reading 7,5.2, and 4.1 amps when RLA is 12.8; with 5 degrees of subcooling. Ambient is 80 in parking garage.Suction head = h s = p s / ρg + v s2 / 2 g. From the definition of vapor pressure head, Vapor pressure head = h v = p v / ρg. In the simplest language, we can say, NPSH = Pressure head at the inlet or suction – vapor pressure head. Let’s see the formula or equation of NPSH, NPSH = hs – hv.The most common, and obvious, reason for a service call is a space temperature that is too warm. And, just as common, is suction pressure and/or head pressure being involved in the cause. Often, the refrigeration system will still run, but it’ll run inefficiently because the suction pressure is too high while the head pressure is ...The users should set high and low alarms on the EdP output to keep the DP tightly controlled while increasing the flow rate. If the pump doesn’t generate 120 feet total head at the 55 gpm flow rate, this could be your first indication of an operational or mechanical issue. Check the suction pressure and ensure it is greater than NPSHr.Head pressure 190 Suction Pressure 90 Suction line temp 54 inside temp 75 wetbulb 69 So ive been thru this problem b4 with the low head high suction so i assume piston or a-coil . I open up the duct and the other hvac guy has put in a 3ton acoil . I told the neighbor that he should replace the acoil with a 2 1/2 ton .Greetings, I am working on a R22 Lennox Split Heat Pump 3 ½ ton. The unit will trip on the compressor relief valve in heating. I was unable to test the unit S/C and S/H accurately, due to the High Side pressure building up so fast with in a minuet will be hitting 400psi and blow the low side would sit at about 50psi. I tested the RVR from cooling to …Jul 20, 2021 · An R-22 evaporator running at 40F saturation temperature will have a corresponding pressure of 68.5 psig. Should the suction pressure drop below 57 psig, the coil temperature will drop below 32F causing moisture in the air to freeze on it (see Figure 4) causing no end of trouble. A R-410A evaporator running below 100 psig will freeze-up just ... Attach a drum of proper, clean refrigerant to the center port of the charging manifold with one of the charging hoses. Attach a second charging hose to the suction gauge (low pressure) side of the gauge manifold. Remove the cap from the suction line valve. Loosely attach the suction gauge hose to the line valve.Feb 26, 2022 · High head suction pressure. High suction pressure is a common problem in the cooling systems. It can cause due to improper functioning of the compressor. If the compressor is not delivering sufficient refrigerant to the system, the suction pressure will increase accordingly. One can understand the high head suction pressure with a better study ... Two types of headaches are caused by a change of pressure inside your skull: Low-pressure headaches (your doctor may call them spontaneous intracranial hypotension, or SIH) and...High head pressure. A hydrostatic tube test kit will. Determine if a tube leaks. When leak testing a low pressure centrifugal chiller with nitrogen what is the maximum test pressure. 10 psig. A ruptured disc on a recovery vessel for …How to Fix Low Suction Pressure Issues. If there is excessive moisture in system: replace the drier. If you find a flattened or kinked hose: replace the hose. If the compressor pistons have worn out: replace the compressor. If there is a shortage of refrigerant: add refrigerant. If there is a leaking compressor head gasket: replace the head gasket.60 ton split.2 circuits. both have high head and low suction. circuit 1 300#hp-35 suction. circuit 2 325 head-38 suction. R-22. fan belt is tight. evap is clean. both circuits flashing at sight glass. 85 ambient.200 ft. pipe run at same elevation.unit has history of failing compressors.unit also has history of normal suction pressures.Figure 5 The effect of low level on the pump suction. The pump will still produce the same total head but the discharge head will go down. This means you may not have enough pressure to run your devices and you may need to consider getting a pump with a higher total head. ... After all if you have a high head, which means a high pressure ...Jan 1, 2013 · The outdoor TXV is stuck open, you can try putting the bulb in ice water to see if TXV closes and also putting the bulb in hot water to see if it opens. Watch your suction pressure. You need to check airflow, you should be moving 1400 cfm. Put unit in emergency heat mode and check temp rise. Both fans working fine. Good air flow through evaporator and condenser. There are no leaks, and no icing. I have tried adjusting the charge to raise the low side pressure, but in doing so would also raise the high side exponentially. (i.e. Increase the suction pressure by 20 psi, and the head pressure would jump as much as 150 psi)Lennox Learning Solutions teaches you what causes high head pressure on a heat pump in the heating mode.There is several factors that can cause hight pressur...Low suction pressure high head pressure is a common issue that can occur in an air conditioning (AC) system. This condition is characterized by a decreased …Feb 26, 2022 · High head suction pressure. High suction pressure is a common problem in the cooling systems. It can cause due to improper functioning of the compressor. If the compressor is not delivering sufficient refrigerant to the system, the suction pressure will increase accordingly. One can understand the high head suction pressure with a better study ... I arrive to find a loud compressor, 200 psi suction and 275 head. First thing that comes to mind is bad valves. A few minutes later the compressor cuts off on internal overload. I take a hose and cool it off. 10 min later, compressor kicks back on and pressures now seem normal (130/325) 13 subcool , 19 delta t. There are three main reasons why a reciprocating compressor will simultaneously have a low head pressure and a high suction pressure. • Bad (leaky) compressor valves; • Worn compressor piston rings; and KITCO NEWS -- Gold slightly pressured Tuesday, and iiTrader’s senior strategist Bill Baruch says it's because of the downward pressure lower copper and crude prices are having ...units are pressure units, not head units. For simplicity, I’ll stick with NPSH, regardless of the units used. Suction Pressure: The First Half of the NPSH Equation Suction pressure must be determined at the pump suction nozzle when the pump is running. If suction pressure is measured with a gauge, the atmospheric pressure (at the pump location)Dec 25, 2023 · Low suction pressure and high head pressure occur when there’s a drop in refrigerant pressure in the AC system, coupled with elevated output pressure in the compressor. The primary culprit behind this condition is a faulty or malfunctioning TXV valve . You are showing low head. Look at it this way. If everything is working properly you would have 8°-12° SC and 10°-20° SH. So lets look at just the SH side first. …Study with Quizlet and memorize flashcards containing terms like 1. A typical setting for the high pressure cut-out control on a recovery unit used for evacuating the refrigerant from a low pressure chiller is: A) 2 psig. B) 5 psig. C) 10 psig. D) 15 psig, 2. A charged low pressure refrigeration system can be efficiently leak checked by: A) adding compressed …In the cooling mode, running in outdoor temperatures below 55 degree without a "low ambient control' will cause symptoms very similar to low refrigerant. The cold outside air will cause the head pressure to drop which, in-turn, causes the suction pressure to drop. Try blocking part of the outdoor fan discharge to increase head …Scroll Troubleshooting Solution Chart - Copeland A/C Specific. Deep Vacuum Conditions. Deep vacuum can cause arcing damage to the Fusite pins. Models built after September 1991 have an internal vacuum protection and stop pumping when the pressure exceeds approximate. 10:1. Scroll compressors should never be used to evacuate a system, allowed to ...This would typically cause a low suction pressure, and a low superheat. In heat mode, a dirty air filter causes low airflow across the condenser. This can cause extremely high head pressure. In heat …An over-charged system will cause efficiency problems and can cause component damage, but the most obvious sign of an over-charge in heating mode, is that it will trip on high head pressure. Jeff Rosenblum. Technical Support. 16 Years Industry Experience. Cell (330) 962-2491.lower suction pressure and high discharge pressure. Study with Quizlet and memorize flashcards containing terms like which of the following is NOT a symptom of a hermetic system that is low on refrigerant?, frost on the suction line indicates;, an increase in head pressure causes _____ refrigerant to flow through a capillary tube. and more.This will cause low suction pressures, high superheats, low amp draws, and low head pressures. Also, the symptoms of a restricted TXV system are very similar to a system with a refrigerant undercharge. However, the undercharged system will have low subcooling levels. Technicians often confuse an undercharged system with a restricted metering ...33 posts · Joined 2011. #7 · Jul 4, 2011. " high head, low suction". 310 isn't high, unless the outdoor temp is 70F which probably isn't the case. Typical condensing temps for 13 SEER cooling equipment is 15-20 degrees above outdoor temp. The saturated temp for 310psi is right at 99F.Mar 7, 2022 · Low suction pressure causes. low suction pressure is developed in the refrigeration system. Some of the most probable causes are as below, The coil is covered with dust or frost. Restriction in the refrigerant line. Filters and strainers are dirty. Faulty fan motor. Low room temperature. Faulty compressor. The suction pressure, also known as the low-side pressure, for a 404A cooler typically falls between 55-70 psi. This pressure ensures that the refrigerant evaporates at the desired temperature in the evaporator, providing efficient cooling. ... What causes high head pressure on a walk-in cooler? High head pressure in a walk-in cooler can be ...This will result in the evaporator being starved, which will cause low suction pressure and high superheats. At the same time, subcooled liquid will be backed up in the condenser, causing higher …A ratio of head pressure to suction pressure is your compression ratio. Higher compression ratios tend to lead to reduced compressor performance (moving fewer BTUs). Even though we tend to see high head pressure as the main problem to avoid, we should be aware that low head pressure is possible.Low wedge sandals are a great way to add a touch of style and comfort to any outfit. Whether you’re headed to the office, out for a night on the town, or just running errands, thes...After the system runs for a while, raise the RPMs up to about 1,500. The system should be about 25 to 30 psi on the low side and 200 to 250 psi on the high side. If the ambient temperature is higher or lower than normal (70 to 80°F) the pressures will go up or down accordingly.May 5, 2016 · The SC might be normal , but the normal head for a r410 system w/ a 68* ambient should be closer to 300psi and the normal suction press should be closer to 110psi w/70* IDB. Those p/t's sound more like r22. kdean1, buttwheat liked this post. As others have said it sounds like a TXV and maybe low on juice. Number 2 is incorrect, metering device part depends on system to system. High load is correct. Look at your liquid line temps, subcooling and approach temps. They will help diagnose high head issues. There is another cause of high head pressure, mismatched (higher btu) compressor. Different refrigerant in the system.I have a suction pressure of 70, converted temp of 41, suction line temp of 51, head pressure of 250, converted temp of 117, head line temp of 96. Air entering condenser is 82 and exit is 100. Air entering evaporator is 76 and exiting is 52.Although cryptos enjoyed strong performances earlier, a lack of fundamental catalysts may apply some pressure on the sector. The fiat alternative narrative isn’t quite panning out ...Low-pressure vapor 3. It can be reasonably assumed that a refrigeration system has an adequate refrigerant charge when all the following criteria are met, except for _____. a. Bubbles in the sight glass b. No bubbles in the sight glass c. Proper head pressure d. Proper suction pressure 4. When a refrigeration system that produces low or no ...High discharge temperatures can indicate minimal movement of refrigerant. Because the refrigerant isn't being pumped at design rates it stays in the condenser for a longer period of time and is cooled more, hence lower head pressures, and in turn, if the compressor is not pumping well, you will see elevated suction pressures. Reply.1 Answer. Hi, High head and a low suction pressure can indicate a couple of different things. One, condenser coil very dirty and needs to be washed very well. This will bring your head pressure down but let it run back up to normal engine temperatures. If the head is ok after you clean it, and suction is even lower, you may still be low on charge.An R22 walk-in refrigerator is running at 50°: The head pressure is 200 psig The suction pressure is 60 psi Which of the following is most likely causing the coil to ice up? Do not have enough information to diagnose it. A medium temperature reach-in with a cap tube is running at 50° box temperature: ...Condensing pressure: High-side pressure, head pressure, discharge pressure. Evaporating pressure: Low-side pressure, suction pressure, back pressure. Figure 1. ... refrigerant liquid and vapor can exist in either high- or low-pressure sides on the refrigeration system. Refrigerant Conditions Along with refrigerant pressures and …When it comes to building a deck, there are many options available. One of the most popular places to shop for decking boards is at Lowes. Lowes has a wide selection of decking boa...I will be sharing a pressure chart that may help you troubleshoot low pressure symptoms, high pressure symptoms. As well as other potential problems you may run into when trying to get your r410a or r22 systems …410a low suction pressure. I injected super seal in a 410a system that had a tiny leak that I could not find. 2 years later I come across the problem of low suction pressure normal head pressure. Replaced txv and had same problem. Replaced compressor and had the same problem. Could the super seal be clogging the txv or …

Cause #1 Return Duct Leakage:. The suction pressure can be high if the room temp is high, or the return duct has leaks. Cause #2 TXV Improperly feeding: Cause#3 Outdoor/Indoor coil dirty: low airflow situations can cause refrigerant to not completely condense into a liquid, or turn into a gas Cause #4 Unit is Overcharged: One …. Ingles market greeneville tn

low suction pressure high head pressure

High suction low head, with 100 lb suc and 100 degree ambient your head should be quite a bit higher. Really need the amp draw of comp and rated RLA but appears to be a compressor issue. Im thinking maybe dirty evap i vacuumed rust from drain pain really old unit. I can just about guarantee that thinking is wrong.In addition to a malfunctioning TXV, other factors that can cause high subcooling include a dirty condenser coil or restricted airflow over the condenser. Low Suction pressure/ low head pressure. A bad TXV can also cause low suction pressure and low head pressure in an HVAC system by restricting the flow of refrigerant into the …Second, the pump curve for the 14.125-inch impeller shows that the pump's shutoff head is 212 feet, a 16-foot head increase over the normal pump head of 192 feet at 1,000 gpm. A fluid density of 62 pounds per cubic foot (lb/ft 3 ) would result in a pressure increase of 8.6 pounds per square inch (psi), which is less than the observed 16 psi ...This will result in the evaporator being starved, which will cause low suction pressure and high superheats. At the same time, subcooled liquid will be backed up in the condenser, causing higher …Well, now it has very low suction pressure plus suction-line icing-up; entirely different symptoms: Simple, when checking for restrictions: Refrigerant System RESTRICTIONS, either TXV or FIXED ORIFICE; low suction & head pres.; high superheat & subcooling; low amp draw; icing & poor Relative Humidity Control.High head pressure. A hydrostatic tube test kit will. Determine if a tube leaks. When leak testing a low pressure centrifugal chiller with nitrogen what is the maximum test pressure. 10 psig. A ruptured disc on a recovery vessel for …Definition. of NPSH —The margin of pressure over vapor pressure, at the pump suction nozzle, is Net Positive Suction Head (NPSH). NPSH is the diference between suction …First, we must be aware that a restriction exists in the first place. In the case of the most common liquid line restrictions on HVAC equipment (with no receiver), we will see low suction pressure, high superheat, and normal to high subcooling. (Note: high head pressure isn't typically an indicator of a restriction!) In those cases, we know ...High head pressure. A hydrostatic tube test kit will. Determine if a tube leaks. When leak testing a low pressure centrifugal chiller with nitrogen what is the maximum test pressure. 10 psig. A ruptured disc on a recovery vessel for …By contacting an HVAC technician, you can get your AC system’s suction pressure back to normal levels. If you are experiencing a problem with your air conditioning or heating call us at 512-336-1431 to schedule an appointment. We’ll be glad to come out and take a look at the issue. 1431-183 A/C & Heating proudly serves Round Rock ...Head pressure: 118F 83 + 35 = 118F more or less shows on the high side gauge if I understand this correctly. Low side pressure: 125 psi = 42 saturation temp. 66.2 low side line temp. High side pressure: 335psi = 104 saturation temp. 83.1 high side line temp. Temp at the vent in rooms: 56.1F + or minus. Temp from supply side: 55.2F.High head pressure. A hydrostatic tube test kit will. Determine if a tube leaks. When leak testing a low pressure centrifugal chiller with nitrogen what is the maximum test pressure. 10 psig. A ruptured disc on a recovery vessel for … I have a suction pressure of 70, converted temp of 41, suction line temp of 51, head pressure of 250, converted temp of 117, head line temp of 96. Air entering condenser is 82 and exit is 100. Air entering evaporator is 76 and exiting is 52. Terms in this set (24) When a redfrigeration systems's suction line is noticeably cold instead of just being cool, it probably contains___refrigerent. low-pressure liquid. When a refrigeration systems's liquid linw is noticably hot instead of just being warm. probably contains ____ refrigerant. high-pressure vapor.R22 boiling point: -40.8 degree Celsius at atmospheric pressure (sea level or 1 ATM) R22 density: 3.66 g/cm 3, in gas form - this is a colorless gas. R22 molar mass: 86.47 g/mol. R22 gas cylinder identification: light green. R2 status: no longer in active use, replaced with R458A.Peal. 3 posts · Joined 2009. #46 · Jul 12, 2009 (Edited) I think bwalley is correct. 3 things will cause high head pressure; poor air flow across condenser, overcharge, or non condensable in system. Recover charge, check system for leaks, pull vacuum, and weigh in new charge.Rupturing of the eardrum can occur from a blow to the head, an object pushed into the ear, severe barometric pressure, inner ear infections or from very loud noises. Rupturing of t....